Manufacturers of Lead Acid Tubular Plate Storage Batteries. Traction,Stationary,UPS, Solar Wind Power.
 
BATTERY SELECTION CHART
 
Discharge time(Min)
5'
10'
15'
30'
45'
60'
90'
120'
180'
240'
300'
360'
420'
480'
600'
 
K-FACTOR
0.94
1.06
1.19
1.50
1.76
2.00
2.50
3.00
4.00
4.90
6.10
7.00
8.20
9.10
10.00
 
BATTERY CAPACITY                                   DISCHARGE CURRENT UNDER LOAD - (Amps)
 
20
AH
21
19
17
13
11
10
8
7
5
4
3
3
2
2
2
40
AH
43
38
34
27
23
20
16
13
10
8
7
6
5
4
4
60
AH
64
57
50
40
34
30
20
20
15
12
10
9
7
7
6
80
AH
85
75
67
53
45
40
32
27
20
16
13
11
10
9
8
100
AH
106
94
84
67
57
50
40
33
25
20
16
14
12
11
10
120
AH
128
113
101
80
68
60
48
40
30
24
20
17
15
13
12
140
AH
149
132
118
93
80
70
56
47
3
29
23
20
17
15
14
160
AH
170
151
134
107
91
80
64
53
40
33
26
23
20
18
16
180
AH
191
170
151
120
102
90
72
60
45
37
30
26
22
20
18
200
AH
213
189
168
133
114
100
80
67
50
41
33
29
24
22
20
220
AH
234
208
185
147
125
110
88
73
55
45
36
31
27
24
22
250
AH
266
236
210
167
142
125
100
83
63
51
41
36
30
27
25


66
AH
70
62
55
44
38
33
26
22
17
13
11
9
8
7
7
75
AH
80
71
63
50
43
38
30
25
19
15
12
11
9
8
8
130
AH
138
123
109
87
74
65
52
43
33
27
21
19
16
14
13
135
AH
144
127
113
90
77
68
54
45
34
28
22
19
16
15
14
145
AH
154
137
122
97
82
73
58
48
36
30
24
21
18
16
15
165
AH
176
156
139
110
94
83
66
55
41
34
27
24
20
18
17
 
INVERTER EFFICIENCY 80%
 
UPS/LOAD (VA)
100
150
200
250
300
500
750
***
***
***
***
***
***
***
***
 
BATTERY                                                                   DISCHARGE CURRENT (Amps)
                                 
12
Volts
12
16
21
26
31
52
24
Volts
5
8
10
13
16
26
39
52
36
Volts
5
7
9
10
17
26
35
52
69
48
Volts
5
7
8
13
20
26
39
52
78
60
Volts
5
6
10
16
21
31
42
63
83
104
72
Volts
5
9
13
17
26
35
52
69
87
130
174
96
Volts
7
10
13
20
26
39
52
65
98
130
108
Volts
9
12
17
23
35
46
58
87
116
120
Volts
10
16
21
31
42
52
78
104
144
Volts
13
17
26
35
43
65
87
220
Volts
11
7
23
28
43
57
 
INVERTER EFFICIENCY 85%
 
UPS/LOAD (VA)
100
150
200
250
300
500
750
***
***
***
***
***
***
***
***
 
BATTERY                                                                   DISCHARGE CURRENT(Amps)
                                 
12
Volts
10
15
20
25
29
49
24
Volts
5
7
10
12
15
25
37
49
36
Volts
5
7
8
10
16
25
33
49
65
48
Volts
5
6
7
12
18
25
37
49
74
60
Volts
5
6
10
15
20
29
39
59
78
98
72
Volts
5
8
12
16
25
33
49
65
82
123
163
96
Volts
6
9
12
18
25
37
49
61
92
123
108
Volts
8
11
16
22
33
44
54
62
109
120
Volts
10
15
20
29
39
49
74
98
144
Volts
12
16
25
33
41
61
82
220
Volts
11
16
21
27
40
53